Insul-Sheet® S2S

Made in America

Designed for the HVAC/R Industry

Description

INSUL-SHEET® insulation is an environmentally friendly, CFC-free, flexible elastomeric thermal insulation. It is black in color and supplied as flat sheets (36" x 48") in standard thicknesses of 1/8" thru 2". It is supplied skin two sides in 1/4” and above. INSUL-SHEET® is also available in rolls, with a standard roll width of 48". INSUL-SHEET® is non-porous, non-fibrous and resists mold growth. The Bio-Guard™ antimicrobial system provides added protection against mold, fungal and bacterial growth.  The active ingredient in Bio-Guard™ is registered with the EPA.

Applications

INSUL-SHEET® insulation is used to retard heat gain and prevent condensation or frost formation on cold equipment, tanks, vessels, ducts, or large O.D. pipes. It also effectively retards heat loss when used on hot equipment, ducts, or large pipes. INSUL-SHEET® can be used as duct covering. INSUL-SHEET® is recommended for applications ranging from -297°F to 220°F (-182°C to 104°C) when used as pipe insulation where only the seams and butt joints are glued. On full adhesion applications, the upper limit is 200°F (93°C).

INSUL-SHEET® has a very tough skin which withstands tearing, rough handling, and severe environmental conditions, and yet is quite flexible for easy installation. INSUL-SHEET® has superior cold weather flexibility.

INSUL-SHEET® thickness has been calculated to control condensation on cold surfaces. Refer to the Submittal Sheet for specific recommendations.

Installation

When INSUL-SHEET® Insulation is applied to ductwork and equipment, use a 100% coverage of an approved contact adhesive. With a contact adhesive, both surfaces to be joined should be coated and then joined after the adhesive is dry to the touch. Compression joints with adhesive applied should be used on all butt edges. INSUL-SHEET® is also available with pre-applied pressure sensitive adhesive (PSA) with easy to use release liner. Contact Nomaco K-FLEX for specific installation instructions.

Outdoor Applications

For optimum performance, outdoor applications require R-374 Protective Coating or other recommended protective coating, cladding or jacketing. For more detailed information refer to the Installation Guides.

Resistance to Moisture Vapor Flow

The closed-cell structure and unique formulation of INSUL-SHEET® effectively retards the flow of moisture vapor, and is considered a low transmittance vapor retarder. For most indoor applications, INSUL-SHEET® needs no additional protection.

Additional vapor barrier protection may be necessary for INSUL-SHEET® when installed on low temperature surfaces that are exposed to continuous high humidity.

Flame and Smoke Rating

INSUL-SHEET® Insulation in wall thicknesses of 1" (25 mm) and below has a flame spread rating of 25 or less and a smoke development rating of 50 or less as tested by ASTM E 84 Method of Testing entitled: “Surface Burning Characteristics of Building Materials.”

INSUL-SHEET® Insulation is acceptable for use in duct/plenum applications meeting the requirements of NFPA 90A/B.

Numerical flammability ratings alone may not define the performance of products under actual fire conditions. They are provided only for use in the selection of products to meet limits specified, when compared to a known standard.

Specification Compliance

ASTM C 534 Type 2 (Sheet), Grade 1
ASTM D 1056-00-2C1
New York City MEA 186-86-M Vol. IV
USDA Requirements

UL 94-5V Flammability Classification (Recognition No. E300774)
ASTM E 84 1-1/2" 25/50-tested according to UL 723 and NFPA 255
Complies with requirements of CAN/ULC S102-M88
STC=17 per ASTM E 90

NFPA No. 101 Class A Rating

Meets requirements of NFPA 90A Sect. 2.3.3 for Supplementary Materials for Air Distribution Systems

Meets requirements of ASTM C 411 (Test Method for Hot Surface Performance of High Temperature Thermal Insulation)

Meets requirements of UL 181 sections 11.0 and 16.0 (Mold Growth/Air Erosion)

MIL-P-15280, Form S (Sheet)

R8 Sheet meets R-value requirements of the International Energy Conservation Code for Outdoor Ductwork.

Physical Properties INSUL-SHEET®
Insulation
Test
Methods
Thermal Conductivity (K)
BTU -in/hr - Ft² - °F (W/mK)
90°F (32°C) Mean Temp .270 (.039) ASTM C 177
75°F (24°C) Mean Temp .265 (.038) ASTM C 177
50°F (10°C) Mean Temp .260 (.037) ASTM C 177
Operating Temperature Range
    Flexible to -40°F (-40°C)
Upper 220°F (104°C)  
Lower -70°F (-57°C)  
Water Vapor Permeability Dry Cup. Perm-In <0.06 ASTM E 96
Water Absorption % <0.20 by volume ASTM C 209
Ozone Resistance Pass ASTM D 1171
Chemical/Solvent Resistance Good  
Mildew Resistance/Air Erosion Pass UL 181
Flame Spread (up to 1-1/2" thickness) Not greater than 25 ASTM E 84
Smoke Developed (up to 1-1/2" thickness) Not greater than 50 ASTM E 84